Power entry modules with line filter
EF2
Connectors
* Ambient temperature [°C]
Correction factor
–10
0,89
–5
0,91
0
0,92
+23
1,00
+30
1,03
+40
1,08
+55
1,16
Technical data (continued)
Circuit breaker
Tripping characteristics
In < 3 A
Tripping characteristics
In 3… < 18 A
Tripping characteristics
In 18 A
Type
TA45
Rated current
In <3 A
1 pole protected
2 pole protected
Ambient temp.
+23
°C
10'000
60
2`000
1`000
500
200
100
50
20
10
5
2
1
0,5
0,3
0,2
0,1
[ sec ]
[ min ]
10
5
1
30
20
1,05
Multiple of rated current
[ x In ]
10
8
5
4
3
2
1,32
Tr
ipping
time
Type
TA4 5
Rated current
In ≥ 3 A... < 18 A
1 pole protected
2 pole protected
Ambient temp.
+23
°C
10'000
60
2`000
1`000
500
200
100
50
20
10
5
2
1
0,5
0,3
0,2
0,1
[ sec ]
[ min ]
10
5
1
30
20
1,05
Multiple of rated current
[ x In ]
10
8
5
4
3
2
1,32
Tr
ipping
time
Type
TA4 5
Rated current
In ≥18 A
1 pole protected
2 pole protected
Ambient temp.
+23
°C
Tr
ipp
ing
time
10'000
0
2`000
1`000
500
200
100
50
20
10
5
2
1
0,5
0,3
0,2
0,1
[ sec ]
min ]
0
5
1
0
1,05
Multiple of rated current
[ x In ]
10
8
5
4
3
2
1,32
1)
Effect of ambient temperature
The unit is calibrated for an ambient temperature of +23 °C. To de-
termine the rated current for a lower or higher ambient temperature,
use a correction factor from the table on the right side:
1)
Example
Rated current at +23 °C
6,0 A
Ambient temperature
+40 °C
Correction factor
1,08
Chosen rated current at
+40 °C ambient temperature
6 A x 1,08 = 6,5 A
* Temperature must be measured at the rear of the breaker next to
the terminals after equipment operating temperature has been
reached.
Order code for EF12 (order example)
Type
Order code TA45
(2-pole rocker-switch
without accessories)
EF12. A B T W F 1 5 0 C 0 .
see table 1
11 1 0. 01
Wiring
1 = wired
Protection class
0 = Class I, housing black
Panel mount
0 = Screw-on version
Terminals
1 = Quick connect terminals 6,3 x 0,8 mm
Line filter version
1 = standard
2 = medical
Line filter, rated current
1 = 20 A, 2 = 16 A, 3 = 12 A
Please note that Schurter will establish an internal new part number
for logistical use in addition to the order code. The format of this in-
ternal part number is, for example EF12.xxxx.1110.01
Application note
The rated current of the line filter must be equal or higher than the
rated current of the circuit-breaker
Other versions on request