Rockwell Automation
4-71
Bulletin 100-G
Contactors
4
Specifications
IEC Performance Data
100-G550
100-G700
100-G860
100-G1000
100-G1200
Switching of DC Loads
Switching of non- or slightly inductive loads,
resistance furnaces DC-1 at 60
°C
1-pole
24/48 V
[A]
645
760
930
1 020
1 150
2 Poles in series
24/48 V
[A]
645
760
930
1 020
1 150
3 Poles in series
24/48 V
[A]
645
760
930
1 020
1 150
110 V
[A]
480
560
630
800
900
220 V
[A]
315
400
450
500
600
Shunt Motors
Starting, regenartive brake, reverse,
Jogging DC-3, 60
°C
3 Pole in Serie
24/48 V
[A]
605
800
870
960
1 085
Series-characteristic Motors
Starting, regenartive brake, reverse,
Jogging DC-5, 60
°C
3 Pole in Serie
24/48 V
[A]
605
800
870
960
1 085
Switching of Lamps
Electric discharge lamps AC-5a
Single compensated:
open
[A]
450
570
700
850
1 000
close
[A]
Incandescent lamps AC-5b
360
460
550
660
800
Electrical Lifespan
~ 100 000 operations
[A]
315
440
500
560
630
Switching of Transformers AC-6a
Rated transformer current
[A]
259
330
405
470
570
n = 30
400 VAC
[kVA]
248
315
390
450
540
500 VAC
[kVA]
248
315
390
450
540
690 VAC
[kVA]
225
284
315
450
540
n = 20
[kVA]
389
495
608
700
850
n = 15
[kVA]]
517
660
810
945
1 130
Short-time Withstand ICW, 60 °C
1 s
[A]
5 500
7 000
8 000
10 000
12 000
4 s
[A]
5 500
7 000
8 000
10 000
12 000
10 s
[A]
4 400
5 600
6 900
8 000
9 600
15 s
[A]
3 800
5 000
6 000
7 400
8 500
60 s
[A]
2 300
2 800
3 400
4 000
4 800
240 s
[A]
1 300
1 800
2 000
2 300
2 700
900 s
[A]
850
1 150
1 350
1 600
1 900
Minimum Cooling Time at Zero Current
[Min.]
60
Resistance and Power Dissipation
Main current circuit resistance
[m
]
0.11
0.1
0.08
0.06
0.05
Power dissipation of all at Ie AC-3
[W]
99
147
177
300
318
Total power dissipation
at Ie AC-3
AC control
[W]
110
172
202
370
388
DC control
[W]
109
169
199
360
378
Rated transformer current
Switch-on peak load
= n
Product Selection - Page 4-66