Pressure Sensors
Low-cost, Stainless Steel, Isolated Sensors
13 mm Series
Honeywell
Sensing and Control
3
PERFORMANCE CHARACTERISTICS – UNCOMPENSATED SERIES (1)
Characteristic
Minimum
Typical
Maximum
Unit
Zero pressure offset
-7.5
0
+7.5
mV/V
Pressure non-linearity
(3)
–
±0.1
±0.25
%FSS
Pressure hysteresis
(3)
–
±0.015
±0.030
%FSS
Repeatability
–
±0.010
±0.030
%FSS
Temp. coefficient of span
(4)
(0 °C to 82 °C [32 °F to 180
°F])
360
720
1260
ppm/°C
Temp. coefficient of resistance
(4)
(0 °C to 82 °C [32 °F to 180
°F])
2700
3420
4500
ppm/°C
Temp. coefficient of offset
(4)
(0 °C to 82 °C [32 °F to 180
°F])
–
30
–
V/V/°C
Thermal hysteresis
(0 °C to 82 °C [32 °F to 180
°F])
–
±0.1
±0.3
%FSS
Long-term stability of offset and span
(5)
–
±0.1
±0.3
%FSS
Response time
(6)
–
0.1
–
ms
Input resistance
4.0
4.75
6.0
k
Output resistance
4.0
4.75
6.0
k
PRESSURE RANGE SPECIFICATIONS – UNCOMPENSATED SERIES
Catalog Listing
Pressure range
Full scale span (2)
Proof pressure (7)
Burst pressure (8)
13U 0500P A 0 K
0 psi to 500 psi
175 mV to 300 mV
1200 psi
2400 psi
13U 1000P A 0 K
0 psi to 1000 psi
175 mV to 300 mV
3000 psi
5000 psi
13U 2000P A 0 K
0 psi to 2000 psi
175 mV to 300 mV
6000 psi
10,000 psi
13U 3000P A 0 K
0 psi to 3000 psi
175 mV to 300 mV
9000 psi
10,000 psi
13U 5000P A 0 K
0 psi to 5000 psi
290 mV to 500 mV
10,000 psi
NOTES
1. Reference conditions (unless otherwise noted): T
A = 25 °C [77 °F]; Supply VS = 10 Vdc ±0.01 Vdc or IS = 1.5 mA
±0.0015 mA.
2. Full-scale span (FSS) is the algebraic difference between the output voltage at full-scale pressure and the output at zero
pressure. FSS is ratiometric to supply voltage.
3. Pressure non-linearity is based on best-fit straight line from zero to the full-scale pressure. Pressure hysteresis is the
maximum output difference at any point within the operating pressure range for increasing and decreasing pressure.
4. The error band resulting from maximum deviation of a transducer’s output parameter (offset, span, or resistance) as
temperature is varied from 25 °C [77 °F] to any other temperature within the specified range 0 °C to 82 °C [32 °F to
180 °F]. This parameter is not 100 % tested and is guaranteed by process design and tested on a sample basis only.
Temperature coefficient of span is evaluated using a constant current source.
5. Long-term stability over a six-month period.
6. Response time for a 0 psi to FSS pressure step change, 10 % to 90 % rise time.
7. The maximum pressure that can be applied without changing the transducer’s performance or accuracy.
8. The maximum pressure that can be applied to a transducer without rupture of either the sensing element or transducer
case.