Axial Lead and Cartridge Fuses
424
www.littelfuse.com
Designed to UL/CSA Standards
5 x 20 mm
Fast-Acting Fuse 235 Series
ELECTRICAL CHARACTERISTICS:
% of Ampere
Rating
100%
135%
200%
Opening
Time
4 hours,
Min
imum
1 hour,
Max
imum
5 second,
Max
imum
INTERRUPTING RATING:
0.10-1A
10,000 amperes at 125 VAC, 0.7-0.8 power factor
35 amperes at 250 VAC, 0.7-0.8 power factor
1.25A-3.15A
10,000 amperes at 125 VAC, 0.7-0.8 power factor
100 amperes at 250 VAC, 0.7-0.8 power factor
4A-6A
10,000 amperes at 125 VAC, 0.7-0.8 power factor
ORDERING INFORMATION:
RoHS compliant and Pb-free version available, add XP suffix to
standard catalog number
Designed to UL/CSA/ANCE 248 Standard.
Available in Cartridge and Axial Lead Format.
Available in ratings of 0.100 to 6 amperes.
RoHS compliant and Pb-free version available, add XP suffix to
standard catalog number
Nominal
Nominal
Melting I
2
t
A
2
Sec.
0.00160
0.00280
0.00890
0.0170
0.0330
0.0600
0.0710
0.115
0.160
0.260
0.480
1.12
2.08
2.72
5.59
8.62
17.60
28.15
48.60
Catalog
Number
235
.100
235
.125
235
.200
235
.250
235
.300
235
.400
235
.500
235
.600
235
.700
235
.800
235
001
235
1.25
235
01.6
235
002
235
02.5
235
003
235
004
235
005
235
006
Ampere
Rating
.100
.125
.200
.250
.300
.400
.500
.600
.700
.800
1
1.25
1.6
2
2.5
3
4
5
6
Voltage Resistance
Rating Cold Ohms
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
125
125
125
8.40
5.75
3.15
2.25
1.60
1.08
0.455
0.318
0.263
0.195
0.153
0.106
0.0775
0.0600
0.0438
0.0348
0.0248
0.0185
0.0150
UL
RoHS
ENVIRONMENTAL SPECIFICATIONS:
Operating temperature:
-55C to 125C
Thermal Shock:
MIL-STD-202F Method 107G, Test Condition B: (5
cycles –65°C to +125°C)
Vibration:
MIL-STD-202F Method 201A
Humidity:
MIL-STD-202F Method 103B, Test Condition A. high relative
humidity (95%) and elevated temperature (40°C) for 240 hours.
Salt Spray:
MIL-STD-202F Method 101D, Test Condition B
PHYSICAL SPECIFICATIONS:
Material:
Body: Glass
Cap: Nickel Plated Brass
Leads: Tin Plated Copper
Terminal Strength:
MIL-STD-202F Method 211A,
Test Condition A
Solderability:
Reference IEC 60127 Second Edition 2003-01 Annex A
Terminal strength:
MIL-STD-202F Method 211A, Test Condition A
Product Marking:
Cap 1: current and voltage rating.
Cap 2: Agency approval markings.
Packaging:
Available in Bulk (v=5, H=100, M=1000 pcs/pkg) or on
Tape/Reel (MRET1=1000 pcs/reel).
Pb