![](http://datasheet.mmic.net.cn/160000/54511_datasheet_7969476/54511_1.png)
48
Compression
CAT. NO.
WIRE SIZE
Dimensions in. (mm)
Die Set
Cat. No.
Color
Code
Flex Class G, H, I, K, M*
A
B
54504
#8 AWG
#8 AWG, 37/24, #8 Weld
1.00 (25.4)
0.27 (6.9)
21
Red
54505
#6 AWG
#6 AWG, 61/24, #6 Weld, 133/0.014
1.00 (25.4)
0.30 (7.6)
24
Blue
54506
#4 AWG
#4 AWG, 91/24, 133/0.0177, 49/0.029
1.00 (25.4)
0.37 (9.4)
29
Grey
54507
#2 AWG
125/24, #4 Weld
1.25 (31.8)
0.41 (10.4)
33
Brown
54508
#1 AWG
#2 AWG, 150/24, 175/24, #2 Weld, 133/0.0223
1.50 (38.1)
0.47 (11.9)
37
Green
54509
1/0 AWG
225/24, #1 Weld, 133/0.0254
1.63 (41.4)
0.52 (13.2)
42
Pink
54510
2/0 AWG
1/0 AWG, 275/24, 1/0 Weld, 427/0.0155, 133/0.0282
1.75 (44.5)
0.57 (14.5)
45
Black
54511
3/0 AWG
2/0 AWG, 325/24, 2/0 Weld, 133/0.0316, 259/0.0227, 427/0.0177
1.75 (44.5)
0.63 (16.0)
50
Orange
53962
375/24, 179 kcmil, 133/0.0355, 259/0.0255, 427/0.0199
1.81 (46.0)
0.70 (17.8)
50
Orange
54512
4/0 AWG
3/0 AWG, 450/24, 3/0 Weld, 703/0.0154
1.88 (47.8)
0.70 (17.8)
54
Purple
54513
250 kcmil
4/0 AWG, 550/24, 4/0 Weld, 133/0.0399, 259/0.0286, 637/0.0183
2.25 (57.2)
0.77 (19.6)
62
Yellow
53964
4/0 AWG, 550/24, 4/0 Weld, 133/0.0399, 259/0.0286, 637/0.0183
2.13 (54.1)
0.79 (20.1)
62
Yellow
54514
300 kcmil
–
2.13 (54.1)
0.83 (21.1)
66
White
54515
350 kcmil
–
2.25 (57.2)
0.90 (22.9)
71
Red
54516
400 kcmil
–
2.75 (69.9)
0.93 (23.6)
76
Blue
53968
300 kcmil, 775/24 (313 kcmil)
3.00 (76.2)
1.13 (28.7)
87
Brown
54518
500 kcmil
–
2.75 (69.9)
1.11 (28.2)
87
Brown
54520
600 kcmil
–
3.00 (76.2)
1.18 (30.0)
94
Green
54522-TB
700 kcmil
–
3.25 (82.6)
1.23 (31.2)
99
Pink
53969
1325/24 = 500/535 kcmil, 427/0.0342
3.00 (76.2)
1.24 (31.5)
99
Pink
54523-TB
750 kcmil
–
3.00 (76.2)
1.30 (33.0)
106
Black
54528
1000 kcmil
–
3.63 (92.2)
1.50 (38.1)
125
N/A
54530
1250 kcmil
–
4.13 (104.9)
1.67 42.4)
140
N/A
Connectors for Copper Conductors
Two-Way Splice Connectors – Standard Barrel Certified to 600V
and Recommended up to 35 kV
A
E
Material: High-Conductivity
Wrought Copper
Finish:
Electro Tin Plate
Two-way connectors provide high pullout values,
are easy to insulate and provide a low-resistance
connection of high quality and low installed cost.
CAT. NO.
WIRE SIZE
Dimensions in. (mm)
Die
Code
Color
Code
Flex Class G, H, I, K, M
A
E
54804
#8 AWG
#8, 37/24 = 14.9 kcmil
1.75 (44.5)
0.27 (6.9)
21
Red
54805
#6 AWG
#6, 61/24 = 24.6 kcmil
1.75 (44.5)
0.31 (7.9)
24
Blue
54806
#4 AWG
#4, 91/24 = 36.7 kcmil
1.75 (44.5)
0.39 (9.9)
29
Grey
54807
#2 AWG
125/24 = 50.4 kcmil
1.88 (47.8) 0.43 (11.0)
33
Brown
54808
#1 AWG
#2, 150/24 = 60.5 kcmil
175/24 = 70.6 kcmil
2.00 (50.8) 0.49 (12.4)
37
Green
54809
1/0 AWG
225/24 = 90.8 kcmil
2.00 (50.8) 0.54 (13.7)
42
Pink
54810
2/0 AWG
1/0, 275/24 = 111 kcmil
2.13 (54.1) 0.59 (15.0)
45
Black
54811
3/0 AWG
2/0, 325/24 = 131 kcmil
2.25 (57.2) 0.65 (16.5)
50
Orange
54812
4/0 AWG
450/24 = 182 kcmil
2.75 (69.9) 0.72 (18.3)
54
Purple
54813
250 kcmil
4/0, 550/24 = 222 kcmil
3.38 (85.9) 0.79 (20.1)
62
Yellow
Two-Way Splice Connectors – Long Barrel Certified to 600V and
Recommended up to 35 kV Applications
*Contact Technical Services for specific stranding listings.
Tooling: pp. 112–141
Die Selector Chart: pp. 142–149
Material: High-Conductivity
Wrought Copper
Finish:
Electro Tin Plate
E DIA.
54
DIE
PURPLE
54
DIE
PURPLE
54
DIE
PURPLE
54
DIE
PURPLE
T&B 4/0
A
CAT. NO.
WIRE SIZE
Dimensions in. (mm)
Die
Code
Color
Code
Flex Class G, H, I, K, M
A
E
54814
300 kcmil
250, 650/24 = 262 kcmil
3.50 (88.9)
0.87 (22.1)
66
White
54815
350 kcmil
–
3.75 (95.3)
0.95 (24.1)
71
Red
54816
400 kcmil
775/24 = 313 kcmil
3.75 (95.3)
0.98 (24.9)
76
Blue
54818
500 kcmil
350, 925/24 = 373 kcmil 4.75 (120.6) 1.11 (28.2)
87
Brown
54820
600 kcmil
1100/24 = 444 kcmil
4.25 (108.0) 1.21 (30.7)
94
Green
54823
750 kcmil 500, 1325/24 = 535 kcmil 4.75 (120.6) 1.34 (34.0)
106
Black
58524
1600/24 = 646 kcmil
5.00 (127.0) 1.39 (35.3)
106
Black
58526*
900 kcmil 750, 1925/24 = 777 kcmil 5.50 (139.7) 1.51 (38.4)
115
Yellow
54828
1000 kcmil
–
5.63 (143.0) 1.56 (39.6)
125
N/A
54833
1500 kcmil
–
5.63 (143.0) 1.56 (39.6)
125
N/A
54839
2000 kcmil
–
7.06 (179.3) 2.13 (54.1)
–
N/A
*CSA approved code cable only
Tooling: pp. 108–137
Die Selector Chart: pp. 140–147
For installations from 16 kV up to 35 kV, consult shielded cable manufacturers for stress relief and insulation requirements.
For installations from 16 kV up to 35 kV, consult shielded cable
manufacturers for stress relief and insulation requirements.
For installations from 16 kV up to 35 kV, consult shielded
cable manufacturers for stress relief and insulation
requirements.