System Bus Cable
1/2
for
Data Sh eet
WAGO Kontakttechnik GmbH & Co.KG
Postfach 2880 D-32385 Minden
Phone: 05 71 / 8 87-0
E-Mail:
info@wago.com
Hansastr. 27 D-32423 Minden
Fax:
05 71 / 8 87-169 Web:
http://www.wago.com
Subject to design changes
02.06.2010 / d07561305060en
M12 Socket
M12 Plug
Pin assignment
1
2
3
4
5
Description
Item
Pack. unit
no.
pcs
System bus cable, with both ends of cable fitted, B coded,
not drag chain suitable
M12 socket, straight, M12 plug, straight, 0.2 m
M12 socket, straight, M12 plug, straight, 0.3 m
M12 socket, straight, M12 plug, straight, 0.5 m
M12 socket, straight, M12 plug, straight, 1.0 m
M12 socket, straight, M12 plug, straight, 2.0 m
M12 socket, straight, M12 plug, straight, 5.0 m
M12 socket, straight, M12 plug, straight, 10.0 m
M12 socket, straight, M12 plug, straight, 20.0 m
M12 socket, straight, M12 plug, straight, 50.0 m
756-1305/0060-0002
1
756-1305/0060-0003
1
756-1305/0060-0005
1
756-1305/0060-0010
1
756-1305/0060-0020
1
756-1305/0060-0050
1
756-1305/0060-0100
1
756-1305/0060-0200
1
756-1305/0060-0500
1
Short description:
PUR, halogen-free
Free of silicon and CFC
Good resistance to microbes, hydrolysis, oil, ozone and
UV radiation. Good chemical resistance.
Technical data
General
Operating voltage
≤ 60 V
Operating current
4 A acc. to IEC 60512-3
Rated surge voltage
1.5 kV acc. to IEC 61076-2-101
Insulation resistance
≥ 5x10
8
Contact resistance
≤ 10 m acc. to IEC 61076-2-101
Resistance of conductor
≤ 145 /km
Pollution degree
3/2 acc. to IEC 60664-1
Degree of protection
IP67 acc. to IEC 60529
Operating temperature
-25 °C ... +60 °C (static)
Min. bending radius
5 x cable
Cable
Type code
KS-02YS(ST+C)11Y 4x2xAWG26/7-
100 , shielded
Note
Constr. acc. to UL AWM Style 21586
Overall shield
Aluminum-laminated foil and
tinned copper braid, optical
coverage approx. 65 %
Note
Better than Category 5 according to
EN 50228 and IEC 61156
Band width 200 MHz
Conductor
Bare copper wire , AWG 26/7
Insulation
Max. 1.0 mm, foamed PE
Outer jacket
Halogen-free polyurethane (PUR)
flame resistant acc. to IEC 60332-1-2
Color
Yellow, RAL -1021
Cable diameter
Approx. 6.0 mm
red
white/blue
blue
white/orange
orange
white/green,green,white/
brown,brown
shielded
()