Power Entry Modules with Line Filter
DD22
EMC Products
IEC Appliance Inlet C14 with Filter, Fuseholder 1- or 2-pole, Line Switch 2-pole, for PCB Mounting
Fuse drawer must be ordered separately (see
accessories).
Standard- or Medical-Filter
C14
70° C
Description
-PanelMount:
Screw-onmountingonPCB,fromrear-side
-4Functions:
ApplianceInletProtectionclassI,LineSwitch2-pole,Fuseholderfor
fuse-links5x20mm1-or2-pole,Linefilterinstandardandmedical
version
-PCBsolderterminals
Approvals
-VDECertificateNumber:40001522
-ULFileNumber:E72928
Characteristics
-Ultra-compactdesign.Idealforlowprofiledesigns
-Allsingleelementsarealreadywired
-Foraddedsafety"Extra-Safe"fusedrawersareavailable
FusedrawermeetsrequirementsofmedicalstandardIEC/EN60601-1
Thefusedrawercanonlybeopenedwiththeaidofatool
Thefuseholderisaccessiblefromtheequipmentfront
-Idealforapplicationwithhightransientloads
-QualifiedforuseinequipmentaccordingIEC/EN60950
Other versions on request
-Fusedrawer1-pole,plussparefusecase
-Fusedrawer2-pole,withshortingbar
-Otherrockermarking
-Lineswitch,illuminated
-Lineswitch1-pole
-MedicalversionM80
-ProtectionclassII,70°C
References
Alternative:versionwithoutlinefilter
DD21Weblinks
Technical Data
RatingsIEC
1-10A@Ta40°C/250VAC;50Hz
RatingsUL/CSA
1-10A@Ta40°C/250VAC;50/60Hz
LeakageCurrent
standard<0.5mA(250V/60Hz)
medical<5A(250V/60Hz)
DielectricStrength
>1.7kVDCbetweenL-N
>2.7kVDCbetweenL/N-PE
Testvoltage(1min/50Hz)
AllowableOperationTemp.
-25°Cto85°C
ClimaticCategory
25/085/21acc.toIEC60068-1
DegreeofProtection
fromfrontsideIP40acc.toIEC60529
ProtectionClass
Suitableforapplianceswithprotection
class1acc.toIEC61140
Terminal
ForPCBmounting3mmadditional
quickconnect6.3x0.8mm
PanelThicknesss
Screw-onmounting:max3mm
Mountingscrewtorquemax0.5Nm
Material:Housing
Thermoplastic,black,UL94V-0
Appliance-Inlet/-Outlet
C14acc.toIEC/EN60320-1
UL498CSAC22.2no.42(forcold
conditions)pin-temperature70°C,10A,
ProtectionClass1
Fuseholder
1or2pole,ShocksafecategoryPC2
acc.toIEC60127-6,
forfuse-links5x20mm
RatedPowerAcceptance@
Ta23°C
5x20:2W(1pole)/1.6W(2-pole)per
pole
PowerAcceptance@Ta>
23°C
Admissiblepoweracceptanceathig-
herambienttemperatureseederating
curves
LineSwitch
Rockerswitch2-pole,non-illuminated,
acc.toIEC61058-1
LineFilter
StandardandMedicalVersion,IEC
60939,IEC60601-1,UL1283,UL544,
EN133200,CSAC22.2no.8
MTBF
>2'000'000hacc.toMIL-HB-217F