OUTPUT SPECIFICATIONS
Voltage set point
-48V ±0.1V @ 10A
Total regulation
(Full load to no load)
Main output
Auxiliary output, 5V, 0.5A max. ±5.0%
±5.0%
Rise time
At turn-on
1.0s, max.
Transient response
Main output
75% to 100%
step at 0.1A/μs
5.0% max. dev.,
1ms recovery
Ripple and noise
(20MHz)
Main output
1.0V pk-pk,
Overvoltage protection
latching
-57V to -60V min.
Output power limit
1200W
Short circuit protection
Yes
Current sharing
±10% sharing
0.1V/A droop
1/3L to FL
INPUT SPECIFICATIONS
Input voltage range
1000W
1200W
90 to 264VAC
108 to 264VAC
Input frequency range
47Hz to 63Hz
Input surge current
25°C cold start
36A typ.
Input surge
300VAC
20ms
Safety ground
leakage current
254.4VAC, 50Hz
2.5mA
Input current
90VAC, 1000W
14A rms max.
Input fuse
Replaceable
20A
Power factor
110VAC
220VAC
0.99
0.98
DPF1000 SERIES
Dual output
[ 2 YEAR WARRANTY ]
1000W front end
EN61000-3-2 compliant
11 x 6.0 x 5.0 inch size
Hot pluggable
N+1 redundancy
Full set of status signals
EN55022, EN55011 conducted emissions level A
UL, VDE and CSA safety approvals
The DPF1000 is a 1000W universal input AC/DC front end power supply in a fully
enclosed hot pluggable case with built-in fan, handle, IEC input connector, on/off
switch and DIN output signal connector. Providing dual 48V and 5V outputs with a full
set of status signals. The DPF1000 is designed for use as a front end in medium
power communication applications adopting distributed power architecture. The
DPF1000 is fully compliant with EN61000-3-2. Standard features include current
sharing and full protection against overvoltage, overload and short circuit. Remote or
local system monitoring is possible via a full set of status signals that include fan fail,
DC good, power fail, remote inhibit and current monitoring. The DPF1000, with full
international safety approval and the CE mark, meets conducted emissions EN55022
level A. The DPF1000 can be used in conjunction with our complete range of 3 to
200W DC/DC converters to fully configure a distributed power system.
SPECIFICATION
All specifications are typical at nominal input, full load at 25
°
C unless otherwise stated
PAGE 1
Notes
1
3 orthogonal axes, random vibration, 10 minute test per axis.
EMC CHARACTERISTICS
Radiated noise
Conducted noise
EN55022/11, FCC part 15
EN55022/11
FCC part 15
Level A
Level A
Level A
Compliant
Level 3
Harmonic current emm. EN61000-3-2
Electrical fast
transients/bursts
Surge susceptibility
EN61000-4-4
EN61000-4-5
Level 3
GENERAL SPECIFICATIONS
Hold-up time
110VAC, 60Hz
20ms @ 1000W
Efficiency
110VAC @ 1kW
77% min.
Isolation voltage
Input/output
Input/chassis
3000VAC
1500VAC
Switching frequency
200kHz
Approvals and
standards
VDE0805, EN60950, IEC950
UL1950, BABT
CSA C22.2 No. 950
Weight
4.3kg (9.5Ibs)
MTBF
MIL-HDBK-217F
@ 25°C full load
80,000 hours
ENVIRONMENTAL SPECIFICATIONS
Thermal performance
Operating ambient, FL
Non-operating
50°C to 70°C
ambient
0°C to +50°C
-40°C to +70°C
Derate linearly
to 50% at +70°C
Cooling
Built-in fan
Relative humidity
Operating
5% to 85% RH
Altitude
Operating
Non-operating
10,000 feet max.
30,000 feet max.
Vibration (See Note 1)
5Hz to 500Hz
2.4G rms peak
Shock
MIL-STD-810E
516.4 Part IV