ELECTRICAL SPECIFICATIONS
TELEDYNE RELAYS
Industrial Solid State Products
Industrial Solid State Products 800-436-8766 www.teledynerelays.com
page 11
INPUT (CONTROL) SPECIFICATIONS
Load Voltage/
Parameter
Input Code
Min
Max
Units
600240D
3
32
1200480D
3
32
1600660D
4.5
32
Control Voltage Range
600240R
4
26
Vdc
1200480R
4
26
1600660R
5
26
A
90
280
Vac
Input Current
D,R(@5Vdc)
15
A(@90Vac)
15
Must Turn-Off Voltage
D,R
1
Vdc
A
10
Vac
Reverse Voltage
D,R
-32
Vdc
Protection
A
N/A
Turn-Off Current
D,R
0.25
mA(DC)
A
2.5
mA(AC)
OUTPUT (LOAD) SPECIFICATION
Parameter
Voltage Code
Min
Max
Units
600240
24
280
Load Voltage Rating
1200480
48
530
Vac
1600660
60
660
Frequency Range (Note 2)
47
400
Hz
600240
600
Over Voltage Range
1200480
1200
VPeak
1600660
1600
On-State Voltage Drop
1.7
V
@ Max Rate Current
Turn-On Time
D,A
8.3
ms
R
0.02
ms
Turn-Off Time
8.3
ms
Leakage Current (Off-State)
5
mA
@25
°C
dV/dt (Typical)
500
V/
s
Isolation (All Terminals
To Heatsink) = VRMS
For 1 Min With Unit
Mounted Properly
4000
V
Operating Temperature
-40
125
°C
Power Factor Range
0.5
1.0
OUTPUT (LOAD) SPECIFICATIONS (Contd)
Parameter
Output Current Min
Max
Units
Output Current Rating
150
0.05
150
A
(Load Current @85
°C)
Surge Current Rating
150
1600 A
See Fig 1 (Non-
Repetitive 16.7 mS)
Thermal Resistance
150
0.25
°C/W
Junction to Case (J
C)
NOTES:
1.) Where overvoltage transient spikes are present,
suppression may be required. A suppressor and/or a
snubber circuit across the AC terminals of the module will
provide additional transient immunity.
2.) For 400 Hz inductive load, contact factory.
EFR Series
SINGLE SCR OUTPUT TO 150 AMPS 1600 VOLTS
mA
100
10
1
3500
3000
2500
2000
1500
1000
500
0
150A
FIGURE 1 Max Non-Repetitive Surge Current
Number of Equal Amplitude Current Pulses at 60Hz
Max
On-State
Surge
Current
(Amps
RMS)