FXP7000 AC-DC Series Data Sheet
MCD10162 Rev. 1.0, 04-Jun-10
Page 2 of 8
www.power-one.com
Output Specifications
PARAMETER
DESCRIPTION/CONDITIONS
MIN
NOM
MAX
UNITS
Output Voltage
An additional 1.0 Volt is provided to the output terminals to provide for
45.6
48
50.4
V
Adjustment Range
load lead losses.
Output Power
Continuous duty rating.
7000
Watts
Output Current
Continuous duty rating.
145
A
Efficiency
Full rated load (208Vac).
88
91
%
Regulation
Load, Maximum deviation with 0 to 100% load change:
With Remote Sense connected:
0.2
With Remote Sense not connected:
0.75
%
Utilizing Droop Current Share:
2.0
Line, Under all specified operating conditions.
0.2
Ripple & Noise
Measured at mating connector w/ 0.01F + 10F Tant.
20 MHz BW:
1
% p-p
100 MHz BW:
2
Overshoot / Undershoot
Output voltage overshoot/undershoot at turn-on.
0
%
Minimum Loads
Minimum loading required to maintain regulation.
0
A
Transient Response
Maximum recovery time, to within 1% of initial set
Time:
800
s
point due to a 25% load change, 1A/S.
Deviation:
3.2
%
Turn-On Delay
Time required for initial output voltage stabilization after power-up.
3
s
Turn-on Rise Time
Time required for output voltage to rise from 10% to 90%.
100
ms
Interface Signals and Protection
PARAMETER (NOTE 1,2)
DESCRIPTION/CONDITIONS
MIN
NOM
MAX
UNITS
AC Power Fail Warning
Warning provided prior to Vout dropping 5% after loss of AC input.
4
ms
Auxiliary Power
Output voltage - diode isolated. Inclusive of line, load, and initial tolerances.
11.6
12.0
12.4
V
Output current.
500
mA
Current Monitor
Monitor output current over a compliance range of 0~10V.
Normal output:
0.10
mA/A
Total error current:
0.5
0
0.5
mA
Current Share
Static sharing deviation as a percent of full-load rating
Active:
5
%
for loads >10%.
Passive:
10
Input Range Select Status
Maximum signal resistance in high input voltage range selection.
0.10
Loss of Phase Warning
Warning provided prior to protective reduction in current limit.
500
ms
Output Inhibit
Voltage required to enable supply (0.5 mA sink). (NOTE 3)
1.0
V
Output Interlock
Voltage required to enable supply (6 mA sink). (NOTE 3)
1.0
V
Output Overload Protection
Straight line current limit (above approx. 5V Vout).
149
156
A
Output Overload Warning
Signal level on overload.
2.2
V
Output Short Circuit Protection
Occurs on overload when Vout is below approx. 5V.
Iavg:
25
90
A
May operate in burst-mode.
Output Voltage Fault Signal
Deviation from adjusted Vout that is considered as a fault.
±3
±4
±5
%
Output Voltage Margin
Output voltage swing available through Margin pin (analog).
±4.8
±5.0
±5.2
%
Overtemperature/
Time between fault warning and shutdown.
100
ms
Fan Failure Warning
Latching shutdown.
Overvoltage Protection
Latch style overvoltage protection.
55.2
57.6
60.0
V
Power Supply Present Signal
Resistance to logic ground upon insertion of supply.
1000
Remote Sense
Maximum load lead loss compensation (round trip).
1.0
V
NOTES: 1) All logic outputs listed below feature a standard active pull-down output with 0.4V max at 40 mA sink capability, and a 100k pull-up to 5V.
2) In addition to those listed below, signals and front-panel LEDs are provided to indicate: overtemperature/fan fault, AC phase
imbalance, output good, interlock open, and supply inhibited. The FXP also provides 4 LED’s indicating output loading.
3) Both signals must be pulled to logic ground for the unit to operate. Enables are 100% redundant internally for applications where redundant inhibit is desirable.
Contact factory for additional design details.