2
Specifications are subject to change without notice (03.09.99)
Mode of Operation
The I/O-units use three
wires
for the communication
with all the other I/O-units of
an installation, for the sup-
ply of the I/O-units and for
the loads connected to the
outputs of the units. This
implies, that the “common”
of the communication signal
is identical to the “minus” of
the supply.
The DC-supply voltage must
connect
to
through a G 2196 0000 700,
which also performs the chan-
the
system
nel generator function and the
RS485 communication link to
the elevator controller (please
refer to the data sheet for G
21960 000 700 for details)
Each I/O-unit has 2 inputs
(NPN/contact) and 2 PNP-
outputs. Every input and
output is given its individual
address with the coding unit
GAP 1605 (please refer to
the respective data sheet for
details). The ON/OFF-signal
that is applied to the input
of an I/O-unit is associated
to the address given to that
input. Any output of an I/O-
unit that is given the identi-
cal address will now follow
that input signal and switch
its output signal ON or OFF.
This means that a signal
which is input at one loca-
tion (for example as an out-
put from the lift controller)
may be output wherever
required and as many times
as required.
An input pulse stretcher is
used on every input to
assure that the changes of
input signals (even extreme-
ly short ones) are communi-
cated by the system.
The output status of all out-
puts of an I/O-unit may be
pre-defined for cases like
loss of power and loss of
communication. Please refer
to the paragraph “Output
status setting” of the data
sheet for the GAP 1605 to
change the default setting
(all outputs OFF).
Pin Allocation
Terminal
DUP
GND
POW
DC +
I 1
I 2
O 5
O 6
Input/Output
Dupline
signal
Dupline
+ supply GND
Supply IN
DC out
Input 1
Input 2
Output 1
Output 2
Wiring Diagram
DUPLINE
SUPPLY
CHANNEL
GND
I2
I1
DC+
O6
O5
POW
DUP
GND
G 2140 4421 700
Programming Information
GAP 1605
In/out 1
In/out 2
In/out 3
In/out 4
In/out 5
In/out 6
In/out 7
In/out 8
G 2140 4421
Input 1 (I1)
Input 2 (I2)
Not used
Not used
Output 1 (O5)
Output 2 (O6)
Not used
Not used
The table below shows the relation between the inputs/out-
puts of the G 2140 4421 and the In/Out-markings on the
GAP1605.
General Specifications
Power ON delay
Indication for
Supply ON
Dupline
carrier
Environment
Operating temperature
Storage temperature
Humidity
(non-condensing)
Mechanical resistance
Shock
Vibration
Dimensions
Typ. 2 s
LED, green
LED, yellow
-20° to +50°C (-4° to +122°F)
-50° to +85°C (-58° to +185°F)
20 - 80%
15 G (11 ms)
2 G (6 to 55 Hz)
Open PCB 54 x 40 mm
4 pcs. of nylon PA6 snap
locks are included for mount-
ing the PCB in 4.8 holes
50 g
Weight