![](http://datasheet.mmic.net.cn/260000/PIA01CB235A_datasheet_15942708/PIA01CB235A_2.png)
2
Specifications are subject to change without notice (21.10.00)
Range Setting
Centre knob:
Setting of current on relative
scale: from 10 to 110% of the
full-scale value.
Hysteresis:
Approx. 4% of set value, it
can be extended by inserting
a resistor between terminals
Z1, Y1 or 8, 9.
Approx. resistor values:
10%:
180 k
25%:
47 k
50%:
22 k
75%:
15 k
Latch:
< 500
DIA01, PIA01
Mode of Operation
DIA01 and PIA01 monitor
both AC and DC over current
through an internal shunt.
They can monitor AC cur-
rents up to 6000 A when
connected to a suitable cur-
rent transformer.
Example 1
(connection between termi-
nals Z1, Y1 or 8, 9 - latch
function enabled)
The relay operates and latch-
es in operating position
when the measured value
exceeds the set level. Pro-
vided that the current has
dropped min. 4% below the
set point (see hysteresis) the
relay releases when the inter-
connection between termi-
nals Z1, Y1 or 8, 9 is inter-
rupted or the power supply
is interrupted as well.
Example 2 (Stardard CT)
(no connection between ter-
minals Z1, Y1 or 8, 9 - latch
function disabled)
The relay operates when the
current flowing through the
transformer exceeds the set
level. It releases when the
current drops min. 4% below
the set level (see hysteresis)
or when the power supply is
interrupted.
Power supply
Rated operational voltage
through terminals:
A1, A2 or A3, A2 (DIA01)
2, 10 or 11, 10 (PIA01)
Overvoltage cat. III
(IEC 60664, IEC 60038)
724:
B48:
24 VDC ± 20%, insulated
24/48 VAC ± 15%
45 to 65 Hz, insulated
115/230 VAC ± 15%
45 to 65 Hz, insulated
DC supply
2 kV
4 kV
4 kV
B23:
Dielectric voltage
Supply to input
Supply to output
Input to output
Rated operational power
AC
DC
AC supply
4 kV
4 kV
4 kV
4 VA
2 W
Supply Specifications
Reaction time
Alarm ON delay
< 100 ms
(current rising from
-20% to +20% set value)
< 300 ms
(current decreasing from
+20% to -20% set value)
(15 min warm-up time)
± 1000 ppm/°C
± 0.5% on full-scale
Alarm OFF delay
Accuracy
Temperature drift
Repeatability
Indication for
Power supply ON
Output relay ON
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Housing dimensions
DIN-rail version
Plug-in version
Weight
Screw terminals
Tightening torque
LED, green
LED, red
(EN 60529)
IP 20
3 (DIA01), 2 (PIA01)
-20 to 60°C, R.H. < 95%
-30 to 80°C, R.H. < 95%
22.5 x 80 x 99.5 mm
36 x 80 x 87 mm
Approx. 150 g
Max. 0.5 Nm
acc. to IEC 60947
Yes
CE-Marking
General Specifications