參數(shù)資料
型號: PIC01CB48AV0
文件頁數(shù): 3/5頁
文件大?。?/td> 216K
代理商: PIC01CB48AV0
Specifications are subject to change without notice (21.10.00)
3
Selection of measuring range:
The selection between current
and voltage is automatically
selected through the input
connectors.
TRMS or positive/negative
DC monitoring selectable by
short-circuiting terminals Y1
and Z3 (DIC01 only).
DIP-switch selector (1 to 2)
1 2
0.5 to 5 mA AC/DC
-5 to 5 mA DC
0.1 to 1 V AC/DC
-1 to 1 VDC
2 to 20 mA AC/DC
-20 to 20 mA DC
0.4 to 4 V
p
AC
1 to 10 V AC/DC
-10 to 10 V DC
Selection of function:
DIP-switch selector (3 to 6
and 1 A, 2 A)
3
Relay(s) de-energized in
normal condition.
Relay(s) energized in
normal condition.
4
Power ON delay 1 ± 0.5 s
Power ON delay 6 ± 0.5 s
5
Contact input as latch func-
tion enable. When the contact
is closed the latch function is
activated. The reset of the latch
condition occurs when the con-
tact is open or by power down.
Contact input as inhibit of
alarm enable. When the con-
tact is closed the relay remains
in normal position even if the
alarm condition occurs.
6
Set point 1 over voltage/-
current monitoring relay. The
alarm condition occurs when
voltage/current input is over the
set point value.
Set point 1 under voltage/-
current monitoring relay. The
alarm condition occurs when
voltage/current input is under
the set point value.
1A
Set point 2 over voltage/-
current monitoring relay. The
alarm condition occurs when
voltage/current input is over the
set point value.
Set point 2 under voltage/-
current monitoring relay. The
alarm condition occurs when
voltage/current input is under
the set point value.
2A
2 x SPDT relays (DIC01)
1 x DPDT relay (PIC01)
Selection of level, time delay
and hysteresis:
Upper knob:
Setting of hysteresis on rela-
tive scale: 0 to 30% on set
value.
Centre knobs:
Current level setting on rela-
tive scale: 10 to 110% on full
scale.
Lower knobs:
Setting of delay on alarm time
on absolute scale (0.1 to 30 s).
DIC01, PIC01
Function/Range/Level and Time Delay Setting
Mode of Operation (cont.)
it drops below the over volt-
age set level minus hystere-
sis (the hysteresis is the
same for both set levels).
Example 2
(latch enable active - under+under
current - 2 x SPDT relays (1 x
SPDT for PIC01) - TRMS)
DIC01:
Each relay operates
and latches when the current
drops below the respective
set level for more than the re-
spective delay time. Provided
that the current has exceeded
the respective set level plus
hysteresis, each relay releas-
es when the contact input’s
connection is interrupted.
PIC01:
The relay operates
when the current drops
below the higher set level for
more than the respective
delay time. Provided that the
current has exceeded the
higher set level plus hystere-
sis the relay releases when
the contact input’s connec-
tions is interrupted.
Note
Different delay times can be
used for appropriate reaction
according to the set points.
Example 3
(inhibit enable active - over+over
current with MI CT - DPDT
relay (SPDT for PIC01) - TRMS)
Provided that the contact
input’s connection is inter-
rupted, the relay operates
when the current flowing in
the MI CT exceeds the lower
set level for more than the
respective delay time. It
releases when the current
drops below the lower set
level minus hysteresis or
when the contact input’s
pins are connected.
Example 4
(inhibit enable active - over+over
current with A82-10 CT -
DPDT relay (1 x SPDT for
PIC01) - TRMS
Provided that the contact
input’s connection is inter-
rupted, the relay operates
when the current flowing in
the A82-10 CT exceeds the
lower set level for more than
its delay time. It releases
when the current drops
below the lower set level
minus hysteresis or when the
contact input’s pins are con-
nected.
Example 5 (DIC01 only)
(no contact input - under+over
voltage - 2 x SPDT N.D. relays
- plus/minus DC
One relay operates when the
voltage drops below the
under voltage set point for
more than the respective
delay time. It releases when
the voltage exceeds the set
level plus the set hysteresis.
The other relay operates
when the voltage exceeds
the over voltage set point for
more than the respective
delay time. It releases when
the voltage drops below the
set level minus hysteresis.
In this case the spare front
label has to be placed on the
device
for
adjustment.
proper
level
Note
When the inhibit contact is
opened, if the input signal is
already in alarm position, the
delay time needs to elapse
before relay(s) activation.
ON
ON
ON
相關(guān)PDF資料
PDF描述
PIC10F200(中文) 6-Pin, 8-Bit Flash Microcontrollers(6引腳,8位FLASH微控制器)
PIC10F202(中文) 6-Pin, 8-Bit Flash Microcontrollers(6引腳,8位FLASH微控制器)
PIC10F204(中文) 6-Pin, 8-Bit Flash Microcontrollers(6引腳,8位FLASH微控制器)
PIC10F206(中文) 6-Pin, 8-Bit Flash Microcontrollers(6引腳,8位FLASH微控制器)
PIC10F200_07 6-Pin, 8-Bit Flash Microcontrollers
相關(guān)代理商/技術(shù)參數(shù)
參數(shù)描述
PIC01CD48AV0 制造商:Carlo Gavazzi 功能描述:24-48V PROCESS SIGNAL RELAY
PIC0402HP 制造商:SUPERWORLD 制造商全稱:Superworld Electronics 功能描述:MOLDED POWER CHOKE COIL
PIC0402HP100MN 制造商:SUPERWORLD 制造商全稱:Superworld Electronics 功能描述:MOLDED POWER CHOKE COIL
PIC0402HP1R0MN 制造商:SUPERWORLD 制造商全稱:Superworld Electronics 功能描述:MOLDED POWER CHOKE COIL
PIC0402HP1R2MN 制造商:SUPERWORLD 制造商全稱:Superworld Electronics 功能描述:MOLDED POWER CHOKE COIL