Operating information continued
Parallel Operation
Two or more products may be paralleled for redundancy or
increased output power. External active load sharing circuit
are recommended to provide the maximum balanced current
sharing.
Remote Sense
The product has remote sense that can be used to
compensate for voltage drops between the output and the
point of load. The sense traces should be located close to the
PCB ground layer to reduce noise susceptibility. The remote
sense circuitry will compensate for up to 10% voltage drop
between output pins and the point of load.
If the remote sense is not needed +Sense should be
connected to +Out and -Sense should be connected to -Out.
Over Temperature Protection (OTP)
The product is protected from thermal overload by an internal
Over Temperature Protection circuit (OTP). When the PCB
temperature (TC reference point) exceeds the OTP T
threshold value, the output voltage will be gradually
decreased. This will decrease the power loss inside the
DC/DC power module and protect the module from
hazardous temperatures.
Over Voltage Protection (OVP)
The module includes an output Over Voltage Protection (OVP)
function. In the unlikely event of an output over voltage
condition, the OVP circuit will shut down the output voltage.
The module will be latched in “Off” state unless either the
input voltage or RC input is cycled (switched Off and On
again).
Over Current Protection (OCP)
The moduleinclude current limiting circuitry for protection at
continuous overload.
In case of overload, the output voltage will significantly
decrease. The converter will resume normal operation after
removal of the overload. The load distribution should be
designed for the maximum specified output short circuit
current.
Pre-bias Start-up
The module is able to start-up properly under pre-bias output
condition. During the start-up, the module does not sink
current from an external pre-bias source present at the output
terminals.
Power Good
“Power Good” function is provided. It is a “negative logic”
open collector output which can drive to “l(fā)ow” an external
circuit when the module operates normally.
The PG output will turn level “high” during fault conditions
(e.g. over temperature or over voltage) or when the output is
turned off with the remote control.
Auxiliary output voltage (AUX)
The module provides a power source referred to – sense
terminal. It is intended to be used as a power source for
external circuits, e.g. remote control. The auxiliary output
voltage is active whenever an input voltage in range between
from 17V to 40V is provided.
The nominal auxiliary output voltage is 10V. Maximum allowed
load is 50mA.The auxiliary output source is not short circuit
protected. If it is overloaded, the main converter will be
switched off.
An example of a 5V/45mA power supply driven by the
auxiliary output voltage is given in the figure below.
E
PKY 2000 PI series
DC/DC converters, Input 18-36 V, Output 21.5 A/600 W
EN/LZT 146 385 R2A Oct 2008
Ericsson Power Modules AB
Technical Specication
11