![](http://datasheet.mmic.net.cn/260000/PPB02CM23_datasheet_15946293/PPB02CM23_2.png)
2-52
Specifications are subject to change without notice (06.11.00)
Selection of function:
DIP-switch selector (1 to 2)
1
Power ON delay 6 ±0.5 s
Power ON delay 1 ±0.5 s
2
Phase-phase voltage
Phase-neutral voltage
Selection of measuring range:
DIP-switch selector (3 to 4)
34
3 x 208
VAC (M23)
3 x 380
VAC (M48)
3 x 220
VAC (M23)
3 x 400
VAC (M48)
3 x 230
VAC (M23)
3 x 415
VAC (M48)
3 x 240
VAC (M23)
3 x 480
VAC
(DPB02CM48)
Selection of asymmetry and
time delay:
Centre knob:
Setting of asymmetry on rela-
tive scale.
Lower knob:
Setting of delay on alarm time
on absolute scale (0.1 to 30 s).
Function/Range/Level and Time Delay Setting
DPB02, PPB02
Mode of Operation
Connected with the 3 phas-
es (and neutral) DPB02 and
PPB02 operate when all 3
phases are present at the
same
time,
sequence is correct and the
asymmetry is under the set
level.
Asymmetry is defined as fol-
lows:
the
phase
when
phase voltages and also as
measuring
phase-
follows:
when measuring phase-neu-
tral voltages.
If the asymmetry exceeds
the set level the red LED
starts flashing 2 Hz and the
output relay releases after
the set time period. In any
case if phase-neutral mea-
surement is selected both
phase-phase
neutral voltages are moni-
and
phase-
tored. If the phase sequence
is incorrect or one phase is
lost, the output relay releases
immediately. Only 200 ms
delay occurs. The failure is
indicated by the red LED
flashing 5 Hz after the alarm
condition occurs.
Example 1
(mains network monitoring)
The relay monitors asymme-
try, phase loss and correct
phase sequence.
Example 2
(load monitoring)
The relay releases in case of
interruption of one or more
phases or when the asym-
metry exceeds the set level.
Power supply
Rated operational voltage
through terminals:
L1, L2, L3, N
5, 6, 7, 11
Overvoltage cat. III
(IEC 60664, IEC 60038)
(DPB02)
(PPB02)
M23:
208 to 240 VAC ± 15%
45 to 65 Hz
380 to 480 VAC ± 15%
45 to 65 Hz
M48:
Rated operational power
DPB02CM23, PPB02CM23
DPB02CM48, PPB02CM48
13 VA @ 230 VAC, 50 Hz
13 VA @ 400 VAC, 50 Hz
Supplied by L2 and L3
Supply Specifications
Indication for
Power supply ON
Alarm ON
LED, green
LED, red (flashing 2 Hz
during delay time)
LED, yellow
Output relay ON
Environment
Degree of protection
Pollution degree
Operating temperature
IP 20
3 (DPB02), 2 (PPB02)
-20 to 60°C, R.H. < 95%
@ 475 VAC, 65 Hz
-20 to 50°C, R.H. < 95%
@ 550 VAC, 65 Hz
-30 to 80°C, R.H. < 95%
Storage temperature
Housing dimensions
DIN-rail version
Plug-in version
Weight
Screw terminals
Tightening torque
22.5 x 80 x 99.5 mm
36 x 80 x 87 mm
Approx. 120 g
Max. 0.5 Nm
acc. to IEC 60947
Yes
CE-marking
General Specifications (cont.)
ON
ON
Power ON delay
Reaction time
Incorrect phase sequence or
total phase loss
Asymmetry
Alarm ON delay
Alarm OFF delay
Accuracy
Temperature drift
Delay ON alarm
Repeatability
1 s ± 0.5 s or 6 s ± 0.5 s
< 200 ms
< 200 ms (delay < 0.1 s)
< 200 ms (delay < 0.1 s)
(15 min warm-up time)
± 1000 ppm/°C
± 10% on set value ± 50 ms
± 0.5% on full-scale
General Specifications
max{|
V
ph-ph
|}
nom. voltage
max{|
V
ph-n
|}
nom. voltage