PSS, PSK Extended Data Sheet
Positive Switching Regulator (Industrial)
REV. FEB 25, 2004
Page 14 of 19
Standards and Approvals
All switching regulators are UL recognized according to
UL 60950, CAN/CSA C22.2 No. 234-M90 and IEC/EN
60950.
The units have been evaluated for:
Building in,
Operational insulation from input to output and input/out-
put to case,
The use in a pollution degree 2 environment.
Connecting the input to a secondary circuit which is sub-
ject to a maximum transient rating of 750 V.
The switching regulators are subject to manufacturing sur-
veillance in accordance with the above mentioned UL,
CSA and ISO 9001 standards.
Installation Instruction
Installation of the switching regulators must strictly follow
the national safety regulations in compliance with the enclo-
sure, mounting, creepage, clearance, casualty, markings
and segregation requirements of the end-use application.
Check for hazardous voltages before altering any connec-
tions.
The input and the output circuit are not separated. i.e. the
negative path is internally interconnected!
The units should be connected to a secondary circuit. Do
not open any module. Ensure that a unit failure (e.g. by an
internal short-circuit) does not result in a hazardous condi-
tion. See also:
Safety of operator accessible output circuit.
Note: Additional information on input circuitry, grounding
and parallel operation of units is given in:
Technical Infor-
mation: Application Notes.
Protection Degree
The protection degree is IP 30 (equipped with option P: IP
20). It applies only if the module is plugged-in or the female
connector is properly attached to the module.
Isolation
Electric strength test voltage between input intercon-
Safety and Installation Instructions
Connector Pin Allocation
The connector pin allocation table defines the electrical
potentials and the physical pin position on the connector.
Pin 24 (protective earth) is a leading pin, which provides
electrical contact first. The modules should only be wired
Table 11: H15 and H15 S4 connector pin allocation
Electrical Determination
Type H15
Type H15 S4
Pin No.
Ident.
Pin No.
Ident.
Output voltage (positive)
4
Vo+
4/6
Vo+
Output voltage (positive)
6
Vo+
Output voltage (negative)
8
Go–
8/10
Go–
Output voltage (negative)
10
Go–
Crowbar trigger input (option C)
12
C
12
C
Inhibit input
14
i
14
i
R-input (output voltage programming) 1
16
R
16
R
Sense line (negative)
18
S–
18
S–
Sense line (positive)
20
S+
20
S+
Current sharing control input
22
CS
22
CS
Protective ground (leading pin)
24
Input voltage (negative)
26
Gi–
26/28
Gi–
Input voltage (negative)
28
Gi–
Input voltage (positive)
30
Vi+
30/32
Vi+
Input voltage (positive)
32
Vi+
1 Not available with option P
4
4/6
32
30/32
Type H15
Type H15 S4
Fixtures for connector
retention clips V
(see
Accessories)
Fixtures for connector
retention clips V
(see
Accessories)
10010
Fig. 14
View of male H15 and H15 S4 con-
nector
via the female connector H15 or H15 S4 (according to DIN
41612) to ensure requested safety!
nected with output and case: 750 VDC, 1 s. This test is per-
formed in the factory as routine test in accordance with
IEC/EN 60950 and UL 60950 and should not be repeated
in the field. Power-One will not honour any guarantee
claims resulting from electric strength field tests.