Specifications are subject to change without notice (26.10.99)
1
Current and Voltage Controls
3 Phase-phase Max. and Min. Voltage Control
Types S 172, SYY 165
Product Description
3-phase monitoring plug-in
relay for separate upper and
lower voltage control. Often
used where the generated
electrical power is unstable
Ordering Key
Housing
Type
Output
Power supply
Monitoring relay and 3-phased measur-
ing relay for upper/lower phase-phase
voltages control
Measures if all 3 phase-phase voltages are within
set limits
Measures on own power supply
Operates irrespective of phase sequence
Upper and lower limits separately adjustable
Built-in adjustable timer function
Output: 10 A SPDT relay
Plug-in type module
S-housing
LED-indication for power supply and output ON
Power supply is the 3-phased measuring voltage
(or incorrect) in order to se-
cure the equipment. The
S 172 features built-in time
delay.
Type Selection
Plug
Output
Timer
Supply: 220 VAC
Supply: 380 VAC
Supply: 400 VAC
Supply: 415 VAC
Circular
SPDT
Yes
S 172 156 220
S 172 156 380
S 172 156 400
S 172 156 415
Circular
SPDT
No
SYY 165 220
SYY 165 380
SYY 165 415
Input Specifications
Input
Pins 5, 6 & 7
Measuring ranges
(VAC)
Power supply (phase-phase)
Arbitrary phase sequence
3 x 220
± 15%
187-253 323-437 340-460
231-253 399-437 420-460
105-115%105-115%105-115%
187-209 323-361 340-480
85-95%
85-95%
3 x 415
± 15%
353-477
436-477
105-115%
353-394
85-95%
measures average value of
own supply, whereas scale
ranges are calibrated to
rms-value
≤
40 ms
None (supply/elect.)
4 kV (1.2/50 μs) (line/neutral,
line/line), direct connection
to electronics
3 x 380
± 15%
3 x 400
± 15%
Range
Upper level
Scale
Lower level
Scale
Power supply (phase-phase)
85-95%
Range
Upper level
Scale
Lower level
Scale
Voltage interruption
Dielectric voltage
Rated impulse withstand volt.
Output
Rated insulation voltage
SPDT relay
250 VAC (rms)
(cont./elect.)
μ (micro gap)
10 A/250 VAC (2500 VA)
1 A/250 VDC (250 W)
10 A/25 VDC (250 W)
2.5 A/230 VAC
5 A/24 VDC
≥
30 x 10
6
operations
≥
2.5 x 10
5
operations
(at max. load)
≤
7200 operations/h
Contact ratings
(AgCdO)
Resistive loads
AC 1
DC 1
or
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
AC 1
Operating frequency
Dielectric strength
Dielectric voltage
Rated impulse withstand volt.
≥
2 kVAC (rms) (cont./elect.)
4 kV (1.2/50 μs) (cont./elect.)
(IEC 60664)
Output Specifications
S 172 156 220