K-148
Frequency/Rate Meter
K3NR
I
Initial Settings
I
Parameters
K3NR
Note:
If there are large
discrepancies in the
display select or .
Note, however, that the
maximum counting
frequency is 30 Hz.
Set value menu
Option menu
1 s
Hysteresis
Output pattern
Remote/local programming
Power failure memory
Setting Mode
Prescaling
To display rotational speeds, circumferential speeds, or other
values based on input pulse calculations, the rotational speed
must be multiplied by a factor input before the input pulses are
measured. This factor is called
a prescale value.
Auto-zero Time (Set before use.)
In operation modes 1 to 6, the time to force-zero the frequency if
no pulse is received for a specified period can be set. This time
is called the auto-zero time. Set the auto-zero time to a value
that is somewhat longer than the longest input pulse interval. (If
the time setting is too long or if the factory-set value is used, the
display may not return to zero even if no input pulse is
received.)
Time Unit Setting
Setting
Meaning
Proximity Sensor
Rotation speed (rpm) = f
×
60
×
a
Where,
f: Input pulse frequency (p/s)
a: Prescale value
If there are 5 pulses per rotation, then an accurate rotation
speed can be calculated if a = 1/5 (= 0.2 = 2
×
10-1).
In actual application, input as follows:
Mantissa X = 2.0000
Exponent Y = 10-1
Output test
Power ON
Press the Mode Key for 1 s min. to move to the Setting
Mode.
Select the setup menu ( ) with the Mode Key
and set the operating mode, the input type, and other
settings.
If required, set a prescale value in the prescaling menu
( ).
Set comparative set values in the set value menu ( ).
Make settings in the option menu ( ) as required.
If necessary, generate simulated input for testing the output
function in output test ( ).
After completing all the settings, press the ESC Key to
return to RUN Mode.
Measurement starts.
Set in the prescaling menu
Seconds
Minutes
Minutes and seconds
Hours, minutes, and seconds
Note:
The time unit can be set
only if operating mode 6
(passing time) is
selected.
Selecting the Sensor Type
NO: Voltage
pulse H
NC: Voltage
pulse L
No-contact or
Contact input
Power ON
RUN Mode
Refer to Operation in RUN Mode.
Press the ESC Key and Up Key
for 1 s.
1 s
Comparative set
value bank
No key operation for 5 s
(See note 4.)
Comparative
set value HH
No key operation for 5 s
(See note 4.)
No key operation for 5 s
(See note 4.)
Comparative
set value H
Comparative
set value L
Comparative
set value LL
No key operation for 5 s
(See note 4.)
No key operation for 5 s
1 s
Process time for averaging
measured value
No key operation for 5 s
No key operation for 5 s
No key operation for 5 s
No key operation for 5 s
No key operation for 5 s
No key operation for 5 s
No key operation for 5 s
No key operation for 5 s
Startup
compensation time
Upper limit (H) of
linear output range
Lower limit (L) of