2
Specifications are subject to change without notice (26.10.99)
S 172, SYY 165
Reaction time
τ
= 1 s, worst case reaction
time may be up to 5 x
τ
Adjustable delay on release
built-in (0.2 - 10 s)
Note
:
Reaction time + set time
= real delay on release time
Accuracy
OFF delay
10s, -1/+3 on max.
< 0,1s on min.
Delay on release 0.2-10 s. adj.
Time function
(only S 172)
Indication for
Power supply ON
Output ON
Environment
Degree of protection
Pollution degree
LED, green
LED, red
(IEC 60947-1)
IP 20 B (IEC 60529)
(IEC 60664)
1: S 172 380/400/415
SYY 165 380/415
2: S 172 220, SYY 165 220,
-20° to +50°C (-4° to +122°F)
-50° to +85°C (-58° to +185°F)
200 g
UL, CSA
Operating temperature
Storage temperature
Weight
Approvals
Power supply AC types
Rated operational voltage
through pins 5, 6 & 7
Overvoltage cat. III (IEC 60664)
(IEC 60038)
3 x 220 VAC ± 15%,
45 to 65 Hz
3 x 380 VAC ± 15%,
45 to 65 Hz
3 x 400 VAC ± 15%,
45 to 65 Hz
3 x 415 VAC ± 15%,
45 to 65 Hz
≤
40 ms
None (supply/elect.)
220
380
400
415
Voltage interruption
Dielectric voltage
Rated impulse withstand volt. 4 kV (1.2/50 μs) (line/neutral,
line/line), direct connection
to electronics.
Internal measuring circuit is
connected to pins 5 & 7
Rated operational power
5 VA
Sockets
Hold down spring
Mounting rack
Socket covers
Front mounting bezel
Potentiometer lock
S 411
HF
SM 13
BB 4
FRS 2
PL 2
For further information refer to "Accessories".
Accessories
Time/Range Setting
Range setting
Upper potentiometer:
Adjustment of upper limit in
%.
Middle potentiometer:
Adjustment of lower limit in
%.
Hysteresis
≤
2% of rms-value
Time setting
Bottom potentiometer:
Time setting on relative scale
(not SYY 165).
Time
Adjustable delay on release:
0.2 to 10 s
Connected to 3 phases, the S
172 and SYY 165 measure
sinusoidal voltages. The phase
sequence is arbitrary.
The relay operates as long as
all 3 phase-phase voltages
are within the set upper and
lower limits. The two limits
can be adjusted separately.
For S 172 applies that if one
or more of the phase-phase
voltages rises above the up-
per limit or drops below the
lower limit, the relay releases
after the set time period
whereas SYY 165 releases
immediately.
The relay operates again
when all 3 phase-phase volt-
age are within set limits. Hys-
teresis on operate is 2%.
Example 1
Mains monitoring
The relay measures if the 3
phase-phase
voltage
are
within the upper and lower
limits. The limits are adjusted
by the two built-in potentio-
meters.
Example 2
Monitoring load supply
The relay can protect loads,
such as heating elements,
against
overvoltage
thereby against increase in
current, which could other-
wise destroy the heating ele-
ments.
and
Undervoltage to ohmic loads
causes insufficient heating
capacity, and this can also be
monitored.
The relay cannot be used for
load monitoring if the load is a
motor, as the regenerated
phase voltage, at e.g. fuse
breakdown, is indefinable and
dependent on the mechani-
cal performance when the
failure occurs (see S 171).
Mode of Operation
Supply Specifications
General Specifications