Specifications
FX0N-24
MR-DS
FX0N-24
MR-ES/UL
FX0N-24
MT-DSS
FX0N-40
MR-DS
FX0N-40
MR-ES/UL
FX0N-40
MT-DSS
Electrical data
Integrated inputs/outputs
24
40
Power
supply
AC range (+10%, -15%)
—
100–240 V AC
—
100–240 V AC
—
Frequency at AC
Hz —
50/60 (±10 %)
—
50/60 (±10 %)
—
DC range (+20%, -15%)
24 V DC
—
24 V DC
—
24 V DC
Max. input apparent power
18W
50VA
18 W
20 W
50VA
20W
Inrush
current at ON
100V AC
—
30A / 5 ms
—
30 A / 5 ms
—
200V AC
—
50A / 5 ms
—
50 A / 5 ms
—
24 V DC
60 A / 50
s—
60 A / 50
s60 A / 50s—
60 A / 50
s
Allowable momentary power failure time
10
External service power supply (24 V DC)
—
200
—
200
—
Inputs
Integrated inputs
14
24
Min. current for logical 1
mA 3.5
3.5
Max. current for logical 0
mA 1.5
1.5
Response time
For all base units of the MELSEC FX0N series values:10 ms (at time of shipment),partly adjustable between 0 and 15 ms
Outputs
Integrated outputs
10
16
Output type
Relay
Transistor
Relay
Transistor
Max. switching voltage
V Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 – 30 V DC
Max. output
current
- per output
A 2
2
0,5
2
0,5
- per group*
A —
—
0,8
—
0,8
Max. switching
power
- inductive load
VA 80
80
12
80
12
- lamp load
W 100
100
1,5
100
1,5
Response time
ms 10
10
< 0,2
10
< 0,2
Life of contacts (switching times)
For all base units of the MELSEC FX0N series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA
Mechanical data
Weight
kg 0.6
0.6
0.75
Dimensions (W x H x D)
mm 130 x 90 x 87
130 x 90 x 87
150 x 90 x 87
Order information
Art. no. 66657
66656
66658
66660
66659
66661
* This limitation applies only per reference terminal for each group,4 and 8 outputs for relays and 2 and 4 outputs for transistors.Please observe the terminal assignments for the group identification.
Specifications of Base Units
FX0N ¨ FX2N
Base Units FX0N
The FX0N series base units are available with
24, 40 or 60 input/output points.
It is possible to choose between relay and
transistor output type.
Special features:
Integrated serial interface for communica-
tion between PC and HMI
Standard programming unit interface
LEDs for indicating the input and output
status
Detachable terminal blocks at units with
40 and 60 I/Os
Slot for memory cassettes and
real-time clock
MELSEC FX0N/FX2N
BASE UNITS
Specifications
BASICS
X
FX
F
MITSUBISHI ELECTRIC
26