Specifications for Base Units
¨ FX0N FX2N
Specifications
FX2N-16
MR-ES/UL
FX2N-16
MT-ESS/UL
FX2N-32
MR-DS
FX2N-32
MR-ES/UL
FX2N-32
MT-DSS
FX2N-32
MT-ESS/UL
Electrical data
Integrated inputs/outputs
16
32
Power
supply
AC range (+10%,-15%)
100–240 V AC
—
100–240 V AC
—
100–240 V AC
Frequency at AC
Hz 50/60 (
±10 %)
50/60 (
±10%)
—
50/60 (
±10%)
—
50/60 (
±10 %)
DC range (+20 %, -30 %)
—
24 V DC
—
24 V DC
—
Max. input apparent power
30VA
25W
40 VA
25 W
40VA
Inrush
current at ON
AC 100 V
40 A < 5 ms
—
40 A < 5 ms
—
40 A < 5 ms
AC 200 V
60 A < 5 ms
—
60 A < 5 ms
—
60 A < 5 ms
Allowable momentary
power failure time
ms 10
10
5
10
5
10
External service power supply (24 V DC)
mA 250
250
—
250
—
250
Power supply int. bus (5 V DC)
mA 290
290
Inputs
Integrated inputs
8
16
Input current X0
→X7/ X10→∞
mA 7 / 5
7 /5
7/ 5
7 / 5
7/ 5
7 / 5
Min. current for logical 1
X0
→X7/ X10→∞
mA 4.5 /3.5
4.5 / 3.5
Max. current for logical 0
mA 1.51.5
1.51.5
Isolation
Photocoupler isolation between input terminals and PC power for all base units.
Response time
For all base units of the MELSEC FX2N series values:10 ms (at time of shipment),partly adjustable between 0 and 15 ms (REFF,FNC51 = 0 – 60 ms)
Outputs
Integrated outputs
8
16
Output type
Relay
Transistor
Relay
Transistor
ON voltage (max.)
Generally for relay version:< 250 V AC,< 30 V DC;for transistor version:5 – 30 V DC
Max. output
current
- per output
A 2
0.5
2
0.5
-per group
A —
0.8
—
0.8
Max. switching
power
- inductive load
W 80128080
12
- lamp load
W 100
1.5
100
1.5
Response time
ms 10
<0.2
10
<0.2
< 0.2
<0.2
Life of contacts (switching times)
For all base units of the FX2N series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA
Mechanical data
Weight
kg 0.6
0.6
0.65
Dimensions (W x H x D)
mm 130 x 90 x 87
130 x 90 x 87
150 x 90 x 87
Order information
Art. no. 65550
65551
66620
65553
66621
65554
This limitation applies only per reference terminal for each group, 4 and 8 outputs for relays and 2 and 4 outputs for transistors. Please observe the terminal assignments for the group identification.
Available until 07/1998
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
BASE UNITS
Specifications
BASICS
X
FX
F
Base Units FX2N
The FX2N series base units are available with
16, 32, 48, 64, 80 or 128 input/output points.
It is possible to choose between relay and
transistor output type.
Special features:
Exchangable interface modules for direct
mounting into a base unit
Standard programming unit interface
LEDs for indicating the input and output
status
Detachable terminal blocks
Slot for memory cassettes for up to 16 k
steps PLC program
Integrated real-time clock
MITSUBISHI ELECTRIC
28