Compact Extension Units
FX0N FX2N
Specifications
FX0N-40
ER-ES/UL
FX0N-40
ER-DS
FX0N-40
ET-DSS
Electrical data
Integrated inputs/outputs
40
Power
supply
AC range (+10%, -15%)
AC 100 – 240 V
—
Frequency at AC
Hz 50/60 (±10%)
—
DC range (+20%, -15%)
—
DC 24 V
DC 24
Max. input apparent power
40VA
20W
20 W
Inrush
current at ON
100 V AC
30 A / 5 ms
—
200 V AC
50 A / 5 ms
—
24 V DC
—
60 A / 50
s60 A / 50s
Allowable momentary
power failure time
ms 10
10
External service power supply (24 V DC)
mA 200
—
Inputs
Integrated inputs
24
Min. current for logical 1
mA 3.5
3.5
Max. current for logical 0
mA 1.5
1.5
Response time
For all base units of the MELSEC FX0N series values:10 ms (at time of shipment)
Outputs
Integrated outputs
16
Output type
Relay
Transistor
Max. switching voltage
Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 – 30 V DC
Max. output
current
- per output
A 2
2
0.5
- per group*
A —
—
0.8
Max. switching
power
- inductive load
VA 80
80
12
-lamp load
W 100
100
1,5
Response time
ms 10
10
< 0.2
Life of contacts (switching times)
For all extension units of the MELSEC FX0N series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA
Mechanical data
Weight
kg 0.6
0.6
Dimensions (W x H x D)
mm 150 x 90 x 87
150 x 90 x 87
Order information
Art. no. 60012
55955
55954
* This limitation applies only per reference terminal for each group,4 and 8 outputs for relays and 2 and 4 outputs for transistors.Please observe the terminal assignments for the group identification.
Extension Units FX0N
The FX0N series extension units are available
with 40 input/output points.
It is possible to choose between relay and
transistor output type.
Special features:
LEDs for indicating the input and output
status
MELSEC FX2N series compatible
Integrated service power supply
with up to 200 mA capacity
MELSEC FX0N/FX2N
EXTENSION UNITS
Specifications
BASICS
X
FX
F
MITSUBISHI ELECTRIC
32