Modular Extension Units
FX0N FX2N
IN
Specifications
FX0N-8
ER-ES/UL
FX0N-8
EX-ES/UL
FX0N-8
EYR-ES/UL
FX0N-8
EYT-ESS/UL
FX0N-16
EX-ES/UL
FX0N-16
EYR-ES/UL
FX0N-16
EYT-ESS/UL
Electrical data
Integrated inputs/outputs
8
16
Power supply
All modulare extension units are supplied by the base unit.
Inputs
Integrated inputs
4
8
—
16
—
Min. current for logical 1
mA 3.5
3.5
——3.5
——
Max. current for logical 0
mA 1.5
1.5
——1.5
——
Response time
For all extension units of the MELSEC FX0N series values:10 ms
Outputs
Integrated outputs
4
—
8
—
16
Output type
Relay
—
Relay
Transistor
—
Relay
Transistor
Max. switching voltage
Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 – 30 V DC
Max. output
current
- per output
A 2
—
2
0.5
—
2
0.5
- per group*
A —
—
0.8
—
0.8
Max. switching
power
- inductive load
VA 80
—
80
12
—
80
12
- lamp load
W 100
—
100
1.5
—
100
1.5
Response time
ms 10
10
< 0.2
10
< 0.2
Life of contacts (switching times)
For all extension units of the MELSEC FX0N series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA
Mechanical data
Weight
kg 0.2
0.2
0.3
Dimensions (W x H x D)
mm 43 x 90 x 87
43 x 90 x 87
70 x 90 x 87
Order information
Art. no. 60023
60013
60014
60016
55952
55951
55950
* This limitation applies only per reference terminal for each group,4 and 8 outputs for relays and 2 and 4 outputs for transistors.Please observe the terminal assignments for the group identification.
Extension Units FX0N
The FX0N series modular extension units are
available with 8 or 16 input/output points.
It is possible to choose between relay and
transistor output type.
Special features:
LEDs for indicating the input and output
status
MELSEC FX2N series compatible
Vertically mounted (at 8 I/Os) or horizon-
tally mounted (at 16 I/Os) terminal blocks
with a cable guide to the upper or lower
side
MELSEC FX0N/FX2N
EXTENSION UNITS
Specifications
BASICS
X
FX
F
MITSUBISHI ELECTRIC
34